Rockwell Automation Publication 750-TD001H-EN-P - June 2013 37
PowerFlex 750-Series AC Drives
Fusing
The recommended fuse types are listed below. If available current ratings do not match those listed in the tables provided,
choose the next higher fuse rating.
IEC – BS88 (British Standard) Parts 1 & 2, EN60269-1, Parts 1 & 2
(1)
, type gG or equivalent should be used.
UL – UL Class CC, T, RK1, J, or L should be used.
Circuit Breakers
The “non-fuse” listings in the following tables include inverse time circuit breakers, instantaneous trip circuit breakers
(motor circuit protectors) and 140M self-protected combination motor controllers. If one of these is chosen as the desired
protection method, the following requirements apply:
IEC – Both types of circuit breakers and 140M self-protected combination motor controllers are acceptable for IEC
installations.
UL - Only inverse time circuit breakers and the specified 140M self-protected combination motor controllers are
acceptable for UL installations.
(1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.