ASM-40 Ver. 1.0 Site Requirements and Prerequisites 2-1
Chapter 2
Installation and Setup
This chapter describes installation and setup procedures for the standalone
ASM-40 modem.
ASM-40 is delivered completely assembled. It is designed for tabletop or 19-inch
rack installation. For rack installation instructions, refer to the rack mounting kit
for 19-inch racks guide that comes with the RM kit.
After installing the unit, refer to
Chapter 3
to assure normal operation.
In case a problem encountered, refer to
Chapter 4
for test and diagnostic
instructions.
Internal settings, adjustment, maintenance, and repairs may be performed only
by a skilled technician who is aware of the hazards involved.
Always observe standard safety precautions during installation, operation, and
maintenance of this product.
2.1 Site Requirements and Prerequisites
An AC-powered ASM-40 should be installed within 1.5m (5 ft) of an easily
accessible grounded AC outlet. The outlet should furnish 100 VAC to 240 VAC.
A DC-powered ASM-40 unit requires -48 or 24 VDC power source, which must be
adequately isolated from the mains supply. In order to prevent a fire hazard, a
suitable fuse should be installed in the VDC line.
Allow at least 90 cm (36 in) of frontal clearance for operating and maintenance
accessibility. Allow at least 10 cm (4 in) clearance at the rear of the unit for signal
lines and interface cables.
The ambient operating temperature of ASM-40 is 0° to 50°C (32° to 122°F) at
relative humidity of 90%, non-condensing.
Warning